Tysen-kld

DYNAMIC PFC MODULES

Easy Installation & MaintenanceFor Frequently Changing Loads

BKT+M series dynamic compensation modules form a filter circuit by capacitors, filter reactors, thyristor switches, fuses and connecting wires. It is mainly applicable to occasions with extremely fast changing load and great consumption of reactive power, such as spot welding machine etc..

Energy Saving

Adopting reactive compensation technology can improve power transmission and distribution capacity, reduce equipment investment, improve voltage quality, suppress interference, etc..

Solution Characteristics

  • Compact structure, small floor area
  • Easy installation and maintenance
  • Good heat dissipation performance
  • Easy to assemble, disassemble and maintain
  • High degree of operation security
  • Low capacitor loss, safe and stable
  • Fast switching capacitor bank number
  • Conform to IEC, IEEE , GB standard, etc

Application Areas

KLD-BKT+M series dynamic filter compensation module has excellent dynamic reactive power compensation performance, and has wide applicability, can be used for power distribution system of fast, frequently changing reactive power for various industrial production and civil life under different environment.

  • The module consists with reactance rate of 7%, tuning frequency of 189Hz, can effectively suppress 5th or above harmonic pollution.
  • The module consists with reactance rate of 14%, tuning frequency of 134Hz, can effectively suppress 3th or above harmonic pollution.

Solution Selections

Reactance Rate 7%, Capacitor Un=480V, Over-current Capability: 2.0In

Model Selection Table I for BKT+M Series Compensation Components (with 25kvar as the minimum switching unit)

Compensation
Capacity (kvar)
Steps Model Reactance Rate Configuration System Voltage
50 3 KLD-BKT7-50/3+M-400V 7% 12.5kvar×2+25kvar×1 400
75 4 KLD-BKT7-75/4+M-400V 7% 12.5kvar×2+25kvar×2 400
100 3 KLD-BKT7-100/3+M-400V 7% 25kvar×2+50kvar×1 400
125 3 KLD-BKT7-125/3+M-400V 7% 25kvar×1+50kvar×2 400
150 4 KLD-BKT7-150/4+M-400V 14% 25kvar×2+50kvar×2 400
175 4 KLD-BKT7-175/4+M-400V 14% 25kvar×1+50kvar×3 400
200 5 KLD-BKT7-200/5+M-400V 14% 25kvar×2+50kvar×3 400
225 5 KLD-BKT7-225/5+M-400V 14% 25kvar×1+50kvar×4 400
250 6 KLD-BKT7-250/6+M-400V 7% 25kvar×2+50kvar×4 400
275 6 KLD-BKT7-250/6+M-400V 14% 25kvar×1+50kvar×5 400
300 6 KLD-BKT7-300/6+M-400V 14% 50kvar×6 400
325 7 KLD-BKT7-325/7+M-400V 14% 25kvar×1+50kvar×6 400
350 7 KLD-BKT7-350/7+M-400V 14% 50kvar×7 400

Reactance Rate 14%, Capacitor Un=525V, Over-current Capability: 2.0In

Model Selection Table II for BKT+M series Compensation Components (with 25kvar as the minimum switching unit)

Compensation
Capacity (kvar)
Steps Model Reactance Rate Configuration System Voltage
50 3 KLD-BKT14-50/3+M-400V 14% 12.5kvar×2+25kvar×1 400
75 4 KLD-BKT14-75/4+M-400V 14% 12.5kvar×2+25kvar×2 400
100 3 KLD-BKT14-100/3+M-400V 14% 25kvar×2+50kvar×1 400
125 3 KLD-BKT14-125/3+M-400V 14% 25kvar×1+50kvar×2 400
150 4 KLD-BKT14-150/4+M-400V 14% 25kvar×2+50kvar×2 400
175 4 KLD-BKT14-175/4+M-400V 14% 25kvar×1+50kvar×3 400
200 5 KLD-BKT14-200/5+M-400V 14% 25kvar×2+50kvar×3 400
225 5 KLD-BKT14-225/5+M-400V 14% 25kvar×1+50kvar×4 400
250 6 KLD-BKT14-250/6+M-400V 14% 25kvar×2+50kvar×4 400
275 6 KLD-BKT14-250/6+M-400V 14% 25kvar×1+50kvar×5 400
300 6 KLD-BKT14-300/6+M-400V 14% 50kvar×6 400
325 7 KLD-BKT14-325/7+M-400V 14% 25kvar×1+50kvar×6 400
350 7 KLD-BKT14-350/7+M-400V 14% 50kvar×7 400

For more detailed technical information, please call Tysen-kld.