HIGH-VOLTAGE ARC LIGHT PROTECTION SYSTEMS

Adopting Double-criterion Principle & Fast Relay Triac TechnologyFast & Reliable Action

KLD-AP electric arc fast busbar protection system has fast and reliable action, can effectively reduce the harm caused by arc light to equipment and persons. Adopting fast relay Triac technology to make it have quick protection action, high reliability, and fill in the gaps of medium, low voltage dedicated bus protection.

System Compositions

TYSEN-KLD bus arc light protection system mainly consists of main control system, power supply module, current unit, arc unit, arc detection unit. The transmit the detected arc or current signals to the main control system. After collecting these necessary data, the main control system will output tripping signals to circuit breaker according to actual situation.

I. Main Control System KLD-AP-MCU-H

The main control system is the core component of TYSEN-KLD arc light protection system, and is used to manage, control the whole set of arc light protection system. At the same time, this main control system is provided with RS485 communication interface.

II. Power

It is an independent power supply, and is responsible for supplying power to the main control system, then it is supplied to arc unit and current unit by the main control system.

III. Current Unit KLD-AP-CTE-H

The current unit is used for measuring the current signal of power incoming line cabinet, and ensure the tripping logic operability of arc light protection system under different operation.

IV. Arc Unit KLD-AP-ACU-H

The main control system can extend measuring points via external arc unit.

V. Arc Detection Unit KLD-AP-AS-H

It is the passive arc detection unit specially used for bus protection, and is a light sensing element of arc detection. The arc detection unit can directly send optical signals to the main control system or arc unit.

Technical Parameters

Main Control System KLD-AP-MCU-H

Working Voltage 12VDC Action Time <1ms
Input 16 optical signal input ports (arc detection unit)
4 light integrative input ports
4 data transmission port
Output 4 fast tripping output ports 5A, 600VPP
6 fast tripping output ports 5A,250VAC
1 optical signal output port
RS485 communication interface
Working Temperature 0℃~+75℃ Power Consumption <6W
Dimension Height200mm x Width 90mm x Depth 172mm Weight 1.65kg

Current Unit KLD-AP-CTE-H

Working Voltage 12VDC
Input 5A、2A、1A (Can be set)
1 light integrative signal input port
1 data transmission port
Output 1 optical signal output ports
1 data transmission port
Over-current Setting 50%In-500%In Power Consumption <1W
Dimension Height 190mm x Width130mm x Depth 45mm Weight 0.68kg

Arc Unit KLD-AP-ACU-H

Working Voltage 12VDC
Input 10 optical signal input ports (arc detection unit)
1 light integrative input ports
1 data transmission port
Output 1 optical signal output ports
1 data transmission port
Illuminance Setting 10kLux-50kLux Power Consumption <1W
Dimension Height 190mm x Width130mm x Depth 45mm Weigh 0.65kg

Arc Detection Unit KLD-AP-AS-H

Maximum Connecting Distance ≤100m

Specifications & Model

3kV-35kV High Voltage System

Main Control System KLD-AP-MCU-H

KLD-AP-MCU-H Technical Parameters
1 Voltage 12VDC
2 Power Consumption <6W
3 Action Time <1ms

Arc Unit KLD-AP-ACU-H

KLD-AP-ACU-H Technical Parameters
1 Voltage 12VDC
2 Power Consumption <1W
3 Setting Range 10kLux-50kLux

Current Unit KLD-AP-CTE-H

KLD-AP-CTE-H Technical Parameters
1 Voltage 12VDC
2 Power Consumption <1W
3 Setting Range 50%In-500%In

Arc Detection Unit KLD-AP-AS-H

KLD-AP-AS-H Technical Parameters
The arc detection unit is installed on the partition board between switch cabinet and bus compartment separator.