Automatic fire-extinguishing system of intelligent wireless fire alarm
Integrate "early warning, alarm, and fire-extinguishing" into oneExcellent performance, high reliability, easy installation, use and maintenance
KLD-FAE series automatic fire-extinguishing system of intelligent wireless fire alarm is a new generation of electrical fire alarm and fire protection products integrating microelectronic sensor technology, modern network and wireless communication technology, distributed information processing technology and microcomputer control. It can be used either independently or by networking with the Control Center.
The system is applicable to various fire-fighting environments, e.g. industrial, commercial, government, key projects, residential buildings and other places prone to fire. The wide application of such system can bring great security to users' life and property safety.
System composition
KLD-FAE automatic fire-extinguishing system of intelligent wireless fire alarm mainly consists of three parts: alarm fire-extinguishing system host, alarm fire-extinguishing controller and automatic fire-extinguishing device. It is a complete electrical fire monitor and control system with performance requirements e.g. abnormality warning, fire alarm, automatic fire-extinguishing, system process display and fire record management.
System composition
- KLD-FAE-MC alarm fire-extinguishing system host
The core component of the intelligent wireless fire alarm fire-extinguishing system is the LCD color touch screen for centralized management and monitoring of the whole system. It receives the online alarm data of fire-extinguishing controller, displays the temperature and smoke detection state in real time through wireless transmission mode, and displays and manages the operation states e.g. abnormality warning, fire alarm, automatic fire-extinguishing, fire record, etc. in real time. - KLD-FAE-CT alarm fire-extinguishing controller
The internal fire detector detects the regional environmental temperature, smoke and other signals related to electrical fire hazards in the distribution system, converts them into electrical signals, and judges the fire condition after operation and processing, promptly generates audible and visual alarm, and sends data to the control panel in real time through the wireless module. - KLD-FAE-ED automatic fire-extinguishing device
The device adopts world-leading new environmental protection fire-extinguishing products. It has small size, reliable starting, and high stability, and can extinguish early fires thoroughly, quickly, efficiently and at low cost, so that the device is currently an ideal environmentally-friendly fire-extinguishing system.
Technical Parameters
KLD-FAE-MC alarm fire-extinguishing system host
Working frequency | 50Hz/60Hz±5Hz |
---|---|
Communication | RS232或RS485、GSM |
Wireless communication frequency bands | Dual frequency GSM900MHz and DCS1800 MHz(Phase 2+) |
Alarm Method | 5 alarm phone numbers can be set |
Display | 18'' large LCD touch screen display |
Ambient temperature | -40℃~+85℃ |
Environmental Humidity | Maximum 95%RH (non-condensing) |
Altitude | <1500m (customizable for higher altitude) |
Protection class | IP20 (Other requirements can be customized) |
KLD-FAE-CT alarm fire-extinguishing controller
Working frequency | 50Hz/60Hz±5Hz |
---|---|
Detection Accuracy | ±0.5℃ |
Detection Accuracy | Comply with UL-217 standard |
Wireless communication frequency bands | 433 MHz |
Alarm Method | Sound & light alarm (Optional) |
Alarm intensity | 85 dB (10 feet) |
Ambient temperature | -40℃~+125℃ |
Environmental Humidity | Maximum 95%RH (non-condensing) |
Altitude | <1500m (customizable for higher altitude) |
Protection class | IP20 (Other requirements can be customized) |
KLD-FAE-ED automatic fire-extinguishing device
Protective space | ≤3m3(Others can be customized) |
---|---|
Release time | <10s |
Fire-extinguishing duration | ≤3s(After spraying) |
Spray surface temperature | <90℃ |
Thermal spacing | ≤75°C at 100mm from nozzle |
Product insulation properties | ≥20MΩ |
Validity period | 15 years |
Connection method | Support multi-unit connection |
Ambient temperature | -40℃~+125℃ |
Environmental Humidity | Maximum 95%RH (non-condensing) |
Altitude | <1500m (customizable for higher altitude) |
Protection class | IP20 (Other requirements can be customized) |
Size and Model
KLD-FAE-MC alarm fire-extinguishing system host
Input power supply | 12VDC power supply, AC220V power input, DC12V output current 1A or more |
---|
KLD-FAE-CT alarm fire-extinguishing controller
Input power supply | DC 9V-12V, current 1A |
---|
KLD-FAE-ED automatic fire-extinguishing device
Working voltage | DC12V |
---|---|